6~35Kv Cross-Linked Polyethylene (Xlpe) Insulated Power Cable

Including:

Cross-linked polyethylene insulated power cables with rated voltages of 3.6/6kV, 6/6kV, 6/10kV, 8.7/10kV, 8.7/15kV, 12/20kV, 18/30kV, 21/35kV, and 26/35kV. Application: Mainly used in the lines from substations to user transformers in urban distribution network systems.

Product Details

XLPE Insulated Power Cable:

The conductor XLPE insulated power cable is produced through chemical or physical methods sothat the product is considerably improved in its mechanical performance, thermo-ageing performance and adaptabity, and bears fine electrical performance. It possesses such unique characteristics as the conductor’s high temperature in operation, simple in structure, small in outer diameret, light in weight, convenient in use and free from the restriction of level difference of installation, lt is fit for power distribution and transmission netword of 6-35kV.

Special requirements:

(1) Flame retardant cable Flame-retardant cable in addition to GB/T 12706-2008 standards, its fame-retardant properties conform to GB /T 19666-2005 standard requirements are divided into A, B, C, D four different types of flame-retardant, A, B level for the best-type flame retardant property, C-level for general-type flame-retardant cable, users can select according their requirement, It is also can be made according to BS,DIN,AS/NZS,ANS etc.

(2) LSZH flame retardant cable LSZH flame retardant cable in addition to GB/T 12706-2008 standards, its non-halogen, low smoke and flame retardant properties should conform to GB/T 19666-2005 standard requirements, its flame-retardant properties are divided into A, B, C, D four different types of fame-retardant,A, B level for the best type lame retardant property,C-level for general-type flame-retardant cable,customers can select according their requirement It is also can be made according to BS,DIN,AS/NZS.ANS etc.

Technical Parameter: :

(1) Operation temperature
Max. Permissible continuous operating temp.of conductor of6-35kV cable shall not exceed 90°C.

(2) Conductor short-circuit temperature
Not exceeding250°C,max.Sustaining period not exceeding Sseconds

(3)Installation temperature
It should be heated where ambient temperature is below 0°C

(4) Level difference of installation
Not restricted by the difference of level along the route.

(5) Bending radius
Single core):20(d+D)+5%
D=Actual outer diamer of cable sample (mm)
multi core:15(d+D)±5%
D=Actual outer diamer of the conductor (mm)